Dell UPS Site Preparation Guide, EMEA (230V) Revision 2, December 2012
Overcurrent Protection Devices:
All Dell UPS Rack Mount Models (except 5600W Online and 10kW):
In all cases the installation should include a dedicated electrical branch circuit with a 2-pole overcurrent protection
device. The breaker should be wall-mounted and accessible to the operator.
5600W Online and 10kW UPS:
The 5600W online and 10kW UPS does not have an automatic protection device against current backfeed. Dell
recommends installing an external isolating device (see illustration below). After the device is installed, you must add
a warning label with the following wording or the equivalent on the external AC contactor:
RISK OF VOLTAGE BACKFEED. Isolate the UPS before operating on this circuit, then check for hazardous voltage between all
terminals.
OFF
OFF
BATT.EXT
192V 30A
Not For
Current
Interrupting.
20A
250Vac
CIRCUIT
BREAKER
15A 250Vac
CIRCUIT BREAKER
LS1
LS2
Use Copper Conductor Onl y.
Refer to the instruction manual
for the tightening torqu e.
REPO OUTREPO IN
AC INPUT 230V
REPO OUT
REPO IN
EXTENDED BATTERY
V A288 40
OFF
OFF
OFF
OFF
CIRCUIT BREAKER 250V~20A
OUTPUT 250V~20A
CIRCUIT BREAKER 250V~20A
OUTPUT 250V~20A
LS2
CIRCUIT BREAKER 250V~20A
OUTPUT 250V~20A
CIRCUIT BREAKER 250V~20A
OUTPUT 250V~20A
LS1
INPUT 208-240V~
USE COPPER CONDUCTOR ONLY.
REFER TO THE INSTRUCTION MANUAL
FOR TIGHTENING TORQUE
L2-US
N-EU
L1-US
N-EU
REPO OUT
REPO IN
EXTENDED BATTERY
V A288 40
OFF
OFF
OFF
CIRCUIT BREAKER 250V~32A
OUTPUT 250V~32A
CIRCUIT BREAKER 250V~20A
OUTPUT 250V~20A
CIRCUIT BREAKER 250V~32A
OUTPUT 250V~32A
LS2
LS1
INPUT 208-240V~
USE COPPER CONDUCTOR ONLY.
REFER TO THE INSTRUCTION MANUAL
FOR TIGHTENING TORQUE
L2-US
N-EU
L1-US
N-EU
REPO OUTREPO IN
BATT.EXT
192V 30A
Not For
Current
Interru
-pting.
LS2
LS1
Use Copper Conductor Onl y.
Refer to the instruction manual
for the tightening torqu e.
OFF
20A
250Vac
CIRCUIT
BREAKER
OFF
15A 250Vac
CIRCUIT BREAKER
OFF
AC INPUT 230V
REPO OUTREPO IN
Not For
Current
Interru
-pting.
LS2
Use Copper Conductor Onl y.
AC INPUT 230V
Refer to the instructio n manual
for the tightening torq ue.
OFF
15A 250VAC
CIRCUIT BREAKER
OFF
20A
250VAC
CIRCUIT
BREAKER
OFF
LS1
BATT.EXT
216V 30A
LS2
CIRCUIT
BREAKER
250VAC
15A
CIRCUIT
BREAKER
250VAC
20A
BATT.EXT
216V 30A
USE COPPER CONDUCTOR ONLY.
Refer to the instructio n manual
for the tightening torq ue.
INPUT 220-240V~
REPO OUT REPO IN
OUTPUT 220-240V~ 20A
OUTPUT 220-240V~ 15A
LS1
10kW WW Blades
Electrical input top entry
10kW IEC INTL
Electrical input top entry
5,600W Online
Electrical input bottom entry
5,600W Line Interactive
Electrical input bottom entry
4,200W
Electrical input bottom entry
3,750W
Electrical input bottom entry