Dell H965N Power Supply User Manual


 
57
Specifications
|
Table 14. Environmental and Safety
100/120V Models 230V Models
Operating Temperature Up to 1,500 meters: 0°C to 40°C (32°F to 104°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage
Temperature
-15°C to 60°C (5°F to 140°F)
Relative Humidity 0–95% noncondensing
Operating Altitude Up to 3,048 meters (0–10,000 ft) above sea level
Audible Noise Normal mode: less than 40 dBA typical
Battery mode: less than 50 dBA typical
Fan Speed Off: when the UPS is in Standby mode or there is no load
Low speed: when the load is <80%
High speed: when the load is >80% or the UPS is in Battery mode
Surge Suppression ANSI/IEEE C62.41; 2002 Category B
Safety Conformance UL 1778 4th Edition;
CSA C22.2, No. 107.3
UL 1778 4th Edition;
CSA C22.2, No. 107.3;
IEC/EN 62040-1-1; IEC/EN 60950-1
Agency Markings UL, cUL, NOM/NYCE UL, cUL, CE, GS, GOST, BSMI,
S-MARK, KC, CQC, NRCS, SIRIM
EMC FCC, VCCI, ICES-003, BSMI CE, BSMI, CQC, C-tick