Dell R515 Server User Manual


 
Dell
24
PowerEdge R515 Technical Guide
Table 4. 750W Power Supply Specifications
AC Power Supply (per power supply)
Wattage
750W (optional redundant)
Voltage
100240 VAC, auto ranging, 5060Hz
Maximum inrush current
Under typical line conditions and over the entire system
ambient operating range, the inrush current may reach 55A per
power supply for 10ms or less
The R515 Energy Smart 750W Power Supply is certified Gold (80 Plus) and Climate Savers 3. It is certified UL approved
and incorporates PFC logic.
4.3 Heat Dissipation
Redundant power supply (8 hard drive chassis): 2200 BTU/hr maximum
Redundant power supply (12 hard drive chassis): 2450 BTU/hr maximum
4.4 Environmental Specifications
Table 5 details the environmental specifications for operating and storage of the PowerEdge R515.
Table 5. Environmental Specifications
Temperature
Operating
10° to 35°C (50° to 95°F) with a maximum temperature
gradation of 10°C per hour
Note: For altitudes above 2950 feet, the maximum operating
temperature is derated 1°F/550 ft.
Storage
-40° to 65°C (-40° to 149°F) with a maximum temperature
gradation of 20°C per hour
Relative Humidity
Operating
20% to 80% (noncondensing) with a maximum humidity gradation
of 10% per hour
Storage
5% to 95% (noncondensing) with a maximum humidity gradation
of 10% per hour
Maximum Vibration
Operating
0.26 Grms at 5350Hz for 15 minutes
Storage
1.87 Grms at 10500Hz for 15 minutes
Maximum Shock
Operating
One shock pulse in the positive z axis (one pulse on each side of
the system) of 31G for 2.6ms in the operational orientation
Storage
Six consecutively-executed shock pulses in the positive and
negative x, y, and z axes (one pulse on each side of the system)
of 71G for up to 2ms
Square wave shock of 32G @ 270 in/second