Delta Electronics DVPPF02-H2 Network Card User Manual


 
PROFIBUS DP Slave Communication Module DVPPF02-H2
DVP-PLC Application Manual
10
of the master. When DVPPF02-H2 is used as PROFIBUS DP slave, you have to add the GSD file of
DVPPF02-H2 into the configuration tool of PROFIBUS DP master. The GSD file of DVPPF02-H2 is available
for download at Delta’s website http://www.delta.com.tw/
.
6 LED Indicators & Trouble-shooting
There are two LED indicators on DVPPF02-H2, POWER LED and NET LED. POWER LED displays
whether the power supply of DVPPF02-H2 is normal. NET LED displays whether the communication of
DVPPF02-H2 is connected normally.
POWER LED
LED status Indication How to correct
Green light steady on The power is normal. --
Off No power
1. Check if the power of DVP-EH2 is normal.
2. Check if the connection between
DVPPF02-H2 and DVP-EH2 is normal.
NET LED
LED status Indication How to correct
Off No power
1. Check if the power of DVP-EH2 is normal.
2. Check if the connection between
DVPPF02-H2 and DVP-EH2 is normal.
Red light steady on
DVPPF02-H2 is operating but
is not connected to
PROFIBUS DP network.
Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.
Red light flashes
Depending on the value in
CR#251
See the error code table below for how to
correct.
Green light steady on
DVPPF02-H2 is in data
exchange status
--
Error codes
Code Description How to correct
00 DVPPF02-H2 operates normally. --
01 Hardware error
Send your DVPPF02-H2 back to the manufacturer for
repair.
02 PROFIBUS DP watch dog error
Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.
03
Address setting error (0, or exceeding
0x01 ~ 0x7D)
Set the address of DVPPF02-H2 to be within the range
0x01 ~ 0x7D and re-power DVP-EH2.
04 24V low voltage error
Check if the power supply voltage of DVP-EH2 is
normal, and check if DVPPF02-H2 is normally
connected to DVP-EH2.
05 5V low voltage error
Send your DVPPF02-H2 back to the manufacturer for
repair.
7 Application Example I
¡ Target
Complete data exchange between S7-300 (Siemens PLC) and DVP-EH2 (Delta PLC) through PROFIBUS
DP network.