Eaton Electrical 0800-2000 Power Supply User Manual


 
15
Menu 3: System Status Info (continued)
Menu 4: System ID
Item and Sample
Display
Password to
Change
Range Explanation
3 10
% Full Load
pctfload 90 %
No change
allowed.
Not
applicable.
Percent of Full Load. The percentage of the FERRUPS’ total
capacity that your equipment is using.
3 16
EEPROM Stat Word
eeword 0000 hex
3 15
Unit Ambient Temp
ambtemp 23.0 c
3 14
Run Time
runtime 12 m
3 13
Battery Volts
vbatt 48.51 V
3 12
Output Frequency
freqout 60.4 Hz
3 11
Power Factor
powerfact 0.70
No change
allowed.
No change
allowed.
No change
allowed.
No change
allowed.
No change
allowed.
No change
allowed.
Not
applicable.
0.0-150.0
Not
applicable.
10.00-70.00
Not
applicable.
Not
applicable.
A code used to identify the EEPROM configuration of parameters
and logs.
The temperature (in Celsius) inside the FERRUPS. The FERRUPS
will alarm and shut down if this value is too high.
The estimated runtime remaining, that is, the amount of time the
FERRUPS will continue to support your equipment when the
FERRUPS switches to battery power. The FERRUPS will alarm if
this value falls below a preset limit.
The FERRUPS battery voltage. the FERRUPS will alarm if this
value is too low or too high.
During normal operation, this is the frequency of power the
FERRUPS is receiving from the AC input source. If this value falls
outside preset limits, the FERRUPS goes to battery power. When the
FERRUPS is running on battery power, this is the frequency the
FERRUPS is supplying to your equipment.
The power factor of your equipment; the difference in the way it
draws voltage and current. Power factor equals Watts Out (parameter
3 8) divided by VA Out (parameter 3 7).
4 2
Serial Number
serialno 12345678
Item and Sample
Display
Password to
Change
Range Explanation
No change
allowed.
4 1
Model Number
mdlnum
No change
allowed.
5-9999 The FERRUPS model number.
0-99999999 Your FERRUPS unit’s serial number.
4 3
Unit ID
unitid 0002
No change
allowed.
0-9999 This value is used by CheckUPS software.
4 6
Batt Amp Hours
batamphr 31.0 hrs
4 5
Brown Out Level
brownlvl 79.8 V
4 4
Software Version
sftwver 1.15
User
Service
No change
allowed.
10.0-1000.0
74.4-192.0
0-9999
The AC input voltage at which the FERRUPS will switch to battery
power.
The AC input voltage at which the FERRUPS will switch to battery
power.
The version of unit software that your FERRUPS is using.