Eaton Electrical 10000L(XL) Power Supply User Manual


 
10
1) DC breaker must be connected between the battery pack and
the UPS. The capacity of breaker must be not less than the data
specified in the general specification.
2) Set the battery pack breaker in OFF position and connect the
20 pieces of batteries in series
3) You must connect the external battery cable to the battery first,
if you connect the cable to the UPS first, you may encounter the
hazardous of electric shock. The positive pole of the battery is
connected to the10000LXL in parallel with blue and brown wires;
the negative pole of the battery is connected to the 10000LXL in
parallel with black and white wires; the green and yellow ribbon
wire is connected to the ground of the battery cabinet.
3. To complete the connection by plugging the connector of the
external battery cable into the external battery socket of the UPS.
Do not attempt to connect any loads to the UPS now. You should
connect the input power wire to the right position first. And then
set the breaker of the battery pack in the ON position. After that
set the bypass breaker in the ON position. The UPS begins to
charge the battery packs at the time.
The receptacle for
connecting the UPS
The External Battery Cable Diagram For 6000L(XL)/10000L(XL)
(The cable may vary from different XL models)
The blue & brown wires for connection to the positive
terminal of the battery pack output
The green and yellow ribbon wire for
connection to the ground of the battery
cabinet
The black & white wires for
connection to the negative
terminal of the battery pack
output