4
● Electrical performance
Input
Model Voltage Frequency Power Factor
6000L(XL)/
10000L(XL)
Single-phase (46~54)/(56~64)Hz >0.98 (Full load)
● Operating environment
Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following :
Output
Voltage
regulation
Power
factor
Frequency
tolerance
Distortion
Overload capacity
Current
crest ratio
±4% 0.7lag
Synchronized
(46~54)/(56~64)Hz
in Line mode(AC
mode)
±0.1% of normal
frequency in
Battery mode.
THD<3%
Full load
(linear
load)
105%~130% load
transfers to bypass
mode after 10
minutes.
>130% load transfers
to bypass mode after
1 second and
shutdown the output
after 1 minutes
3:1
maximum
Temperature Humidity Altitude Storage temperature
0℃~40℃ <95% <1000m -15℃~40℃
Altitude (M) 1000
1500
2000
2500
3000
3500
4000
4500
5000
Deratingpower
100%
95%
91%
86%
82%
78%
74%
70%
67%