Eaton Electrical ASY0673 Power Supply User Manual


 
INSTALLATION SETUP
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
18
4. Pry the caps out of the bolt access holes.
5. Use a 1/2 hex-style socket wrench to turn each of the four bolts
clockwise. Doing so lowers the casters to allow the cabinet to roll
on the casters.
6. After rolling the cabinet to its intended position, turn all four caster
bolts counter-clockwise until the cabinet rests on the floor. Place a
plastic cap into each bolt access hole.
NOTE If the floor is uneven and the cabinet is tilted or unstable, you may need to place a
thin steel plate under a corner.
Do not use the caster bolts to level the cabinet.
7. After properly positioning and leveling the cabinet, insert power and
battery modules into the cabinet as described in “Power and
Battery Module Installation” on page 67.