Technical Characteristics
Table 16. IEC Non-Fusible/Fusible Disconnect Switches from 32 to 1250 A
ᕃ
Value on left = non-fusible/ value on right = fusible.
ᕄ
Cable vs busbar connection on fusible @ 630A.
ᕅ
Busbar vs cable connection on fusible @ 800A.
Description Catalogue Number
C362UC30
C362UC30CT
C363UC30JT
C363UV30C
C363UV30J
C363UV30CT
C363UV30JT
C362UV60
C363UV60J
C363UV60JT
C362UV100
C363UV100J
C363UV100JT
C362UV200
C363UV200J
C363UV200JT
C362US400
C363UV400J
C363UV400JT
C362US600
C363UF600J
C362US800
C363UF800L
C362US1000 C362US1200
Rating Ampere 32 32 63 100 200 400 600/630 ➀ 800 1000 1250
Rated Insulation
Voltage Ui (V)
800 750 750 750 750 1000 1000 1000 1000 1000
Rated Impulse
Voltage (Uimp)
8 kV 8 kV 8 kV 8 kV 8 kV 12 kV / 8 kV
➀
12 kV 12 kV 12 kV 12 kV
Operation Current (A)
400 V AC – AC 22A
– AC 23A
32
32
32
32
63
63
100
100
200
200
400
400
630
630
800
800
1000
1000
1200
1000
690 V AC – AC 22A
– AC 23A
32
32
32
32
63
63
100
100
200
200
400
200/250 ➀
500/630 ➀
200/630 ➀
630/800 ➀
400/630 ➀
630
400
630
400
Motor Power (kW)
400 V AC – AC 23A 15 15 30 51 100 220 355 450 560 560
500 V AC – AC 23A 18.5 18.5 40 63 140 280 450 560 560 560
690 V AC – AC 23A 25 25 55 90 185 185/220 ➀ 185/600 ➀ 400/600 ➀ 400 400
Maxi. peak let through
current (kA peak)
5.5 7.6 17.6 17.6/22 ➀ 32 48/36 ➀ 48/77 ➀ 75/77 ➀ 75 75
Connection
Minimum Cu
Cable Section (mm
2)
6
6 10 25 50 185 2 x 150 2 x 185 ③ 2 x 240 ––––
Minimum Cu
Busbar Section (mm
2)
–––– –––– ––––
–––
–––– ––––
2 x 30 x 5 ➁ 2 x 40 x 5 2 x 50 x 5 2 x 60 x 5
Rotary Disconnect Switches