Eaton Electrical Disconnect Switches Switch User Manual


 
For more information visit us at: www.eatonelectrical.ca
25
December 2004
– Variable Depth
Technical Data and Specifications
Figure 15. Mounting Dimension Requirements
Table 18. Mounting Dimension Requirements
in Inches (mm)
Table 19. Line Lug Data Dimension A = The required wire
bending spacing selected from Article
430-10 of the National Electrical Code.
Dimension B = Minimum or maximum
depth from inside of flange holding
operating handle to panel where
Disconnect Switch is mounted.
(Variable 7 to 16 inches.)
G
B
A
C
Datum
Datum
E
F
D
1.62
(41.1)
Min.
.62
(15.7)
Disconnect Switch Type A B C D E F G
30A and 60A Non-fusible
30A and 60A Fusible
100A Non-fusible
See
Dimensions
Below
See
Dimensions
Below
1.56
(39.6)
1.56
(39.6)
1.75
(44.5)
.96
(24.4)
.96
(24.4)
1.10
(27.9)
4.00
(101.6)
4.00
(101.6)
5.50
(139.7)
3.50
(88.9)
3.50
(88.9)
3.38
(85.9)
7.12
(180.8)
9.75
(247.7)
7.12
(180.8)
100A Fusible
200A Non-fusible and Fusible
1.75
(44.5)
3.34
(84.8)
1.10
(27.9)
0.63
(16.0)
5.50
(139.7)
8.50
(215.9)
3.38
(85.9)
1.84
(46.7)
11.88
(301.8)
15.50
(393.7)
Disconnect Switch Size Wire Size
30 Ampere
60 Ampere
100 Ampere
200 Ampere
#2 – 14 Cu/Al
#2 – 14 Cu/Al
1/0 – 14 Cu/Al
250 kcmil – #6 Cu/Al
Operating Mechanisms with Disconnect Switches