15
Liebert GXT2 6 kVA 230V
International Model
Liebert GXT2
10 kVA 208V
Liebert GXT2 10 kVA 230V
International Model
Note: Contact your Liebert representative or www.liebert.com for more details.
* Required Paralleling Components
Total Runtime with Internal and
Extended Battery Cabinets/Full Load
POWER DISTRIBUTION
GXT2-6000RT208
Model Number Amp Rating Input Power Connection Output Power Connection
PD-HDWR 30 No Bypass Hardwire Terminals Hardwire Terminals
PD-HDWR-MBS 30 With Bypass Hardwire Terminals Hardwire Terminals
PD-001 30 With Bypass L14-30P (1) L6-30R,(1) L14-30R,
(4) 5-15/20R T-slot
PD-002 30 With Bypass L14-30P (2) L6-20R, (2) 5-15/20R T-slot
PD-003 30 With Bypass L14-30P (2) L6-30R,
(4) 5-15/20R T-slot
PD-004 30 With Bypass L14-30P (4) EN60320 / C19
PD-005 30 With Bypass L14-30P (4) L5-20R,
(2) L5-30R
PD-006 30 With Bypass L14-30P (4) L5-20R, (2) L6-30R
PD-007 30 With Bypass L14-30P (4) L6-20R
GXT2-10000RT208
Model Number Amp Rating Input Power Connection Output Power Connection
PD-101 50 N/A (8) 5-15/20R T-slot, (2) L6-30R
PD-102 50 N/A (4) 5-15/20R T-slot, (4) L6-20R
PD-103 50 N/A (4) 5-15/20R T-slot, (4) L6-30R
GXT2-PP20KRT208
Model Number Amp Rating Input Power Connection Output Power Connection
PD-201 120 N/A (4) 5 - 15/20R T-slot, (4) L6-20R
PD-202 120 N/A (4) 5 - 15/20R T-slot, (4) L6-30R
BATTERY CABINETS
UPS Model Runtime w/Internal Extended Battery
Batteries/Full Load Cabinet P/N Voltage One Cabinet Two Cabinets
GXT2-6000RT208 5 min. GXT2-144VBATT 144 VDC 14 min. 25 min.
GXT2-6000RT230 7 min. GXT2-240VBATT 240 VDC 21 min. 38 min.
GXT2-4500RT230 10 min. GXT2-240VBATT 240 VDC 31 min. 54 min.
GXT2-10000RT208 5 min. GXT2-288RTVBATT 288 VDC 14 min. 25 min.
GXT2-10000R230 NA GXT2-240RVBATT 240 VDC 5 min. 15 min.
GXT2-10000T230 5 min. GXT2-240TBATTCE 240 VDC 23 min. 43 min.
GXT2-10000T220 5 min. GXT2-240TBATTUL 240 VDC 22 min. 42 min.
INTERNATIONAL MODELS
Model Input Voltage / Frequency Output Voltage / Frequency' Output Rating VA/W
GXT2-6000RT230 176 - 276, 50 or 60 Hz, L-L-G 220, 230 or 240 L-L-G 6000/4200
GXT2-4500RT230 176 - 276, 50 or 60 Hz, L-L-G 220, 230 or 240 L-L-G 4500/3150
GXT2-10000R230 176 - 276, 50 or 60 Hz, L-L-G 220, 230 or 240 L-L-G 10000/7000
GXT2-10000T230 176 - 276, 50 or 60 Hz, L-L-G 220, 230 or 240 L-L-G 10000/7000
GXT2-10000T220 176 - 276, 50 or 60 Hz, L-L-G 220, 230 or 240 L-L-G 10000/7000
PARALLEL CAPABILITY GXT2-PP20KRT208
Description Paralleling POD maximum (3) GXT2-10000RT208 connection for 20kVA capacity plus 10kVA
redundancy (requires (1) paralleling cable p/n GXT2-20KPC-6 for connection to each
GXT2-10000RT208)
Rating 20,000VA / 16,000W at 120/208 or 120/240
Unit Dimensions 16.94”w x 9.85”d x 16.61”h [430mm (w) x 250mm (d) x 422mm (h)]
Shipping Dimensions 23.05”w x 16.74”d x 19.38”h [585mm (w) x 425mm (d) x 492mm (h)]
Unit Weight 41.89lb (19kg)
Shipping Weight 48.94lb (22.2kg)
PARALLEL CAPABILITY GXT2-20KPC-6
Description Paralleling cable, approximately 6 feet long
SYSTEM CONFIGURATION
Capacity / Redundancy GXT2-10000RT208 GXT2-288RTBKIT GXT2-PP20KRT208 GXT2-20KPC-6 PD-201
10kVA / 10kVA 2* 4* 1* 2* 1
20kVA / - 2* 4* 1* 2* 1
20kVA / 10kVA 3* 6* 1* 3* 1
Liebert GXT2 6 kVA 208V
168997_SL23172:15615 govern 7/22/08 2:30 PM Page 16