Troubleshooting
33
4.2 Module LED Indication
Every Battery, Power and Control Module features two LEDs to help inform the user of the module
status, as shown below left. Refer to Table 2 for details.
Table 2 Guide to LEDs
Status
LED
(Green)
Fault
LED
(Yellow) Module Status
OFF OFF
Module not inserted into
frame. System is OFF.
OFF ON
Module is initializing
(max 30 seconds*).
FLASHING OFF
Normal Operation
FLASHING FLASHING
Module is in start-up
qualification mode or module
warning. **
FLASHING ON
Module failed and is off-line.
OFF FLASHING
Abnormal operation,
re-insert module.
If this persists, contact
Liebert Global Services at
1-800-543-2378.
ON OFF
ON ON
ON FLASHING
* If this persists for more than 30 seconds, check to verify the
lever is in the down position, otherwise the module is faulty.
** If both green and yellow LEDs are flashing for more than 30
seconds, then reinsert module.
Green Status LED
Yellow Fault LED
Control Module
Green Status LED
Yellow Fault LED
Green Status LED
Yellow Fault LED
Battery Module
Power Module