Specifications and Technical Data
61
15 D, M 240 47 60 208 42 60
15 E, N 480 24 30 480 18 30
15 E, N 600 19 30 600 14 20
15 E, N 220 53 70 220 39 50
10 A, J 208 35 50 208 28 40
10 B, K 480 16 20 208 28 40
10 B, K 600 12 15 208 28 40
10 B, K 220 34 50 208 28 40
10 C, L 480 16 20 480 12 15
10 C, L 600 13 20 600 10 15
10 C, L 220 35 50 220 26 40
10 D, M 480 16 20 208 28 40
10 D, M 600 13 15 208 28 40
10 D, M 208 36 50 208 28 40
10 D, M 220 34 50 208 28 40
10 D, M 240 32 40 208 28 40
10 E, N 480 16 20 480 12 15
10 E, N 600 13 20 600 10 15
10 E, N 220 35 50 220 26 40
Table 30 Maintenance bypass cabinet electrical data (dual input)
kVA Type
System
I/P Voltage
(VAC)
Rectifier
Max Input
Current
Rectifier
Input OCP
CB Size (A)
Bypass
Max Input
Current
Bypass
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output OCP
CB Size (A)
30 F, P 480 42 50 47 50 208 83 125
30 F, P 600 33 40 37 40 208 83 125
30 F, P 208 95 125 107 125 208 83 125
30 F, P 220 90 125 101 125 208 83 125
30 F, P 240 83 100 93 100 208 83 125
20 F, P 480 28 40 31 40 208 55 70
20 F, P 600 22 30 25 30 208 56 70
20 F, P 208 64 80 71.5 80 208 56 70
20 F, P 220 61 80 68 70 208 56 70
20 F, P 240 56 70 62 70 208 56 70
Table 29 Maintenance bypass cabinet electrical data (single input) (continued)
kVA Type
Maintenance
Bypass
I/P Voltage
(VAC)
Bypass Cabinet
Max Input
Current
Cabinet
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output
OCP CB Size (A)