Emerson 5100 Switch User Manual


 
Connectivity Module 7000 & 4000 Series ATSs 2-1
Device Configurator Screen for 7000 & 4000 Series ATSs
The Device Configurator Screen for 7000 & 4000 Series ATSs shows the Group 5 controller configuration
settings (right side) and Connectivity Module (server) configuration settings (left side) for the selected ATS.
Group 5 Controller Configuration (right side)
Enter or change the ATS Name (8 char. max.)and the ATS Location (20 char. max.). Press the Update
button when finished to save the controller configuration changes.
Connectivity Module (server) Configuration (left side)
Several configuration settings must be set appropriately as described below. Press the Update Server button
when finished to save configuration changes.
Device Configurator Screen for 7000 & 4000 Series ATSs
When a Power Manager or Digital Power Meter is connected, additional buttons appear at the bottom of the
Connectivity Module Device Configuration screen.
Additional Buttons on Device Configurator Screen for
7000 & 4000 Series ATSs with Power Manager or Digital Power Meter
A
TS Location
A
TS Name
Serial Port Speed 19200
Consult with your network
administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
10024-65535, but do not
use
ports 14000-14009 or 30718)
Press Update button when finished to
save the configuration changes. Do this
before
you press Update Server button.
After Controller has been updated,
press Update Server button to save
the configuration changes.
Flow Control No flow control
Interface Mode RS485-4 or 2 Wire
Press to configure the Power
Manager or Digital Power Meter.
Press to configure the Group 5 Controller.
3
r
d
party device running own protocols
Encyrption enable check box and
assign an AES port (same range as
TCP port but do not
use the same
port number used for TCP port.)
After Controller, PM, or DPM has
been updated, press Update Server
button to save the configuration
SNMP refer to A
pp
endix A-5