Emerson 5100 Switch User Manual


 
Connectivity Module 7000 & 4000 Series ATSs 2-3
Configurator Screen Input and Output Names for a 7ATB with Power Manager
For 7ATB only (7000 Series Automatic Transfer & Bypass-Isolation Switch), the Power Manager selection
(Accessory 85 suffix letter designation) must be specified. The selection automatically assigns descriptive tags for
the associated inputs and outputs applicable to the chosen accessory. These fields will be pre-populated with their
known designations, but they are editable by the user. The user must press the Update button to save the
configuration selection and any changes.
Refer to the wiring diagram provided with the 7ATB. It shows the specific Accessory 85 suffix letter used. Set the
Power Manager IO Settings to the Accessory 85 specified on the wiring diagram.
The table below shows the descriptive tags assigned for each Accessory 85 selection, which are unique to 7ATBs.
The N/A selection does not provide any descriptive tags.
Accessory 85 Descriptive Tags Assigned
Accessory
I/O
85R 85S 85SB Other
Input 1 Bypass on Normal Bypass on Normal Bypass on Normal Status Input 1
Input 2 Bypass on Emerg Bypass on Emerg Bypass on Emerg Status Input 2
Input 3 Closed Isolation Bypass on Auto Bypass on Auto Status Input 3
Input 4 Open Isolation Close Isolation Close Isolation Status Input 4
Input 5 Open Isolation Open Isolation Open Isolation Status Input 5
Input 6 Test Mode Emergency Accept Emergency Accept Status Input 6
Input 7 Normal Accept Normal Accept Status Input 7
Input 8 Engine Start Engine Start Status Input 8
Output 1 Trsfer To Emerg Trsfer To Emerg Status Output 1
Output 2 Status Output 2
Output 3 Status Output 3
Output 4 Status Output 4
Press Update button when
finished to save the configuration
Example: Accessory 85S selected
Select the Accessory 85 specified on the 7ATB wiring diagram.