Emerson 60HZ Power Supply User Manual


 
Installation
6
1.2 Internal Inspections
1. Remove any packaging material, then visually examine the UPS and battery equipment for
transit damage, both internally and externally. Report any such damage to the shipper and to
Liebert immediately.
2. Check the nameplate inside the cabinet door to verify that the model number and rating
correspond to the ones specified. Record the model number and serial number in the front of this
installation manual. This information is necessary should service be required.
3. Check for loose connections or unsecured components in the cabinet.
4. Check for shipping damage to internal components.
1.2.1 Storing for Delayed Installation
If the equipment will not be installed immediately, it must be stored indoors where the humidity is no
higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect
the Liebert NX from excessive moisture (see 5.2 - UPS Environmental).
1.3 Preliminary Checks
1.3.1 Identification
The equipment supplied has an identification tag on the back of the main door listing the type and
size of the UPS.
1.4 UPS Location
1.4.1 Positioning the UPS
Choose a location for the UPS that offers:
Easy connection to inputs, outputs and auxiliary equipment
Enough space to service the UPS
Air circulation sufficient to expel heat produced by UPS
Protection against moisture and excessive humidity
Protection against dust and other particulate matter
Compliance with fire prevention regulations and practices
Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency
1.4.2 Environmental Considerations
Before installing the Liebert NX, verify that the UPS room satisfies the environmental conditions
stipulated in 5.2 - UPS Environmental, paying particular attention to the ambient temperature
and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to
keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating tempera-
ture within the range of 74-80°F, (23-27°C).
The Liebert NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit
and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or
cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit
must be a minimum of 8 in. (203mm).
See Table 7 for details on heat dissipation.
!
CAUTION
If the battery cabinet must remain disconnected from power for more than six (6) months, the
battery must be recharged before use. To charge the batteries, the battery cabinet must be
connected to the Liebert NX UPS and the UPS must be connected to utility power and started
up because the charger operates only while the Liebert NX UPS is operating.
!
CAUTION
When batteries are installed in a cabinet adjacent to the UPS unit, the battery—not the
UPS—dictates the designed maximum ambient operating temperature.