Emerson 7ADTB Switch User Manual


 
SECTION 2 TESTING & SERVICE
2--1
TRANSFER TEST
Test the Automatic Transfer Switch portion of the 7000
Series 7ADTB at least once a month. This procedure
checks the electricaloperation of theTransfer Switchand
Controller. Put the engine–generator starting control (at
the engine–generator set) in automatic mode.
In the following test the generator will start, the load will
be transferred to t he Emergency source, then back to the
Normalsource. Aninterruptionto the load willoccur, un-
less the the Transfer Switch contacts are bypassed before
the test. See pages 3–1 through 3–4 for bypassi ng & iso-
lating instructions if no interruption of load is required.
Be sure to close the enclosure door
before proceeding to prevent personal injury
in case of electrical sy stem fault.
Perform the five–step Electrical Operation Transfer
Test procedure on page 1–4.
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure
high reliability and long life for the 7000 Series 7ADTB.
An annual preventive maintenance program is recom-
mended.
ASCO Services, Inc. (ASI) is ASCO P ower
Technologies’s national service organization. In the
US ASI can be contacted at 1-800-800-2726 fo r in-
formation on preventive maintenance agreements.
Checklist f or Yearly Inspection
Hazardous voltage capable of causing shock,
burns, or death is used in this switch.
Deenergize both Normal – Emergency power
sources before performing inspections!
Clean the 7ADTB enclosure.
Brush and vacuum away any excessive dust accumu-
lation. Remove any moisture with a clean cloth.
Check the transfer switch contacts.
Bypass, isolate, and withdraw the transfer switch.
Then remove the transfer switch interphase barriers
andcheckthe condition of thecontacts. Replacecon-
tacts when pitted or worn excessively. Reinstall the
interphase barriers carefully. See page 3–4.
Maintain transfer switch lubrication.
If s w itch is s ub jec ted to s evere dust o r abnorm al
operating conditions, renew factory lubric ation o n
all mov em ents and linkag es . Rel ub r ic ate solenoid
oper ato r if TS coil is repl aced. D on ’t use oil ; or d er
lubrication kit 75-100.
Check all cable connections & retighten them.
REPLACEMENT PARTS
Replacement parts are available in kit form. When or-
dering parts provide the Serial No., Bill of Material No.
(BOM), and Catalog No. from the transfer switch name-
plate. Contact your local ASCO Power Technologies
Sales Office or ASI:
In the U nited States
call 1 800 800 ASCO ( 2726 )
In Canada
call 1 888 234 ASCO ( 2726 )
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair
purposes only and should not have to be unplugged. If
the controller must be isolated, follow these steps:
Bypass–Isolation Switch is energized!
Do not touch isolation contact fingers;
shock, burns, or death could result!
Disconnecting the Plugs
1. Bypass and Isolate the Automatic Transfer Switch.
2. Open the uppe r enclosure door.
3. Separate the two quick disconnect plugs by squeez-
ing the latches. Do not pull on the harness wires.
Reconnecting the Plugs
1. The ATS should be still bypassed and isolated.
2. The two harness plugs and sockets are keyed. Care-
fully align the plugs with the sockets and press
straight in until the latches click.
3. Close the enclosure doors.
4. Follow Return to Service i nstructions on page 3–5.
MANUAL L O AD TRANSFER
This procedure manually transfers load to other source if
the Transfer Switch or Controller are out of service.
Close enclosure doors to prevent personal
injury in case of electrical system fault.
1. Bypass t he connected ACTB source. Turn Bypass Han-
dle to EMERGENCY or NORMAL (see page 3–2).
2. Isolate to Test. Turn the Isolation Handle to TEST
position (see page 3–3).
3. Turn the Bypass Handle to OPEN , then to the other
source (see page 3–1). The load will be interrupted.
4. Turn the Isolation Handle clockwise to the CONN
[connected] position (see page 3–4).