Emerson GXT2-10000RT208 Power Supply User Manual


 
Specifications
44
14.0 SPECIFICATIONS
Table 7 UPS specifications
Model Number Liebert GXT2-10000RT208
Model Rating
8000W/8660VA at 127/220 (120 or 240 degrees only)
8000W/8660VA at 120/208 (120 or 240 degrees)
8000W/10000VA at 120/240 (180 degrees)
8000W/10000VA at 115/230 (180 degrees only)
7200W/9000VA at 110/220 (180 degrees only)
6400W/8000VA at 100/200 (180 degrees only)
DIMENSIONS, RACK MOUNT, W x D x H
Unit, in. (mm) 16.93 x 25.98 x 10.5 (430 x 660 x 267); 6U
Shipping, in. (mm) 22.44 x 33.86 x 15.75 (570 x 860 x 400)
WEIGHT lb (kg)
Unit 109 (49.3)
Shipping 118 (53.6)
INPUT AC PARAMETERS
Nominal Operating Frequency 50 or 60 Hz (Factory Default = 60)
Factory Default VAC 120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase
Angle
120 degrees
Allowable Input Phase Angle
120, 180, 240 degrees, Auto-sensing on application of AC
(Restrictions for L-N voltages other than 120 VAC)
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC (May be modified using configuration program)
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)
100% - 91% loading 100 VAC - 140 VAC
90% - 71% loading 90 VAC - 140 VAC
70% - 51% loading 80 VAC - 140 VAC
50% - 31% loading 70 VAC - 140 VAC
30% - 0% loading 60 VAC - 140 VAC
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)
100% - 91% loading 90 VAC - 140 VAC
90% - 71% loading 80 VAC - 140 VAC
70% - 51% loading 70 VAC - 140 VAC
50% - 0% loading 60 VAC - 140 VAC
L1-N, L2-N Max. Allowable VAC 150 VAC
Input Frequency w/o Battery
Operation
40 - 70 Hz
Input Power Connection Hardwire Terminal Block 3W + G (L-L-N-G)
OUTPUT AC PARAMETERS
Factory Default VAC 120/208 VAC @ 120 degrees
L1-L2 Factory Default
Output Phase Angle
120 degrees
Allowable Output Phase Angle 120, 180, 240 degrees Auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC, ±2%
Output Connections
Hardwire Terminal Block 3W + G (L-L-N-G);
also see 7.2 - Output Receptacle Distribution Options
Frequency 50 Hz or 60 Hz, Nominal
Waveform Sinewave
Main Mode Overload 130% for 60 seconds; 200% for 5 seconds with transfer to bypass.