Specifications
45
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise <55 dBA, at 1 meter
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Surge Immunity IEEE/ANSI C62.41 Category A & B
Transportation ISTA Procedure 1A
Table 8 Battery specifications
Model Number GXT2-288RTBKIT—Two Required
DIMENSIONS, W x D x H
Shipping, in. (mm) 11.02 x 24.02 x 15.35 (280 x 610 x 390)
WEIGHT lb (kg)
Unit 78.1 (35.5)
Shipping 83.6 (38)
Type Valve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating (2) x 12 x 12V x 9.0 AH
Battery Manufacturer / Part # Yuasa / REW 45-12 FR
Back-Up Time See Table 6 - Battery run times
Recharge Time 6 Hours to 90% capacity after full discharge into 100% load
Table 9 Optional output distribution specifications—PD-101
Model Number PD-101
DIMENSIONS, W x D x H
Shipping, in. (mm) 8.86 x 10.43 x 7.87 (225 x 265 x 200)
WEIGHT lb (kg)
Unit 3.8 (1.7)
Shipping 5.1 (2.3)
ELECTRICAL SPECIFICATIONS
Amp Rating 60 Amps
Input Power Connections Internal Anderson connectors
Output Power Connection
L1-L2-G (2) L6-30R on a 300mm cord
L1-N-G (4) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
L2-N-G (4) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
Table 7 UPS specifications (continued)
Model Number Liebert GXT2-10000RT208