Emerson NX Power Supply User Manual


 
Operation
9Liebert
®
NX
Figure 7 Load on bypass
2.2 Touchscreen Navigation
Several menu items can be accessed from the main display screen (see Figure 9). These menu items
are detailed in subsequent sections.
2.2.1 Main Display Screen
This is the default screen. It displays the following information:
Bypass Input Voltage
Bypass Input Frequency
•Input Voltage
Input Current
Input Frequency
Output Voltage
•Output Current
Output Frequency
DC Source Voltage
DC Source Current
System Status
System Normal Indicator—When the green status box appears, this means that the system is
operating normally and that no warning or alarm has occurred. During line power failures (with all
other conditions being nominal), this box is replaced by a yellow triangle.
Warning Indicator—This indication is activated by the presence of abnormal conditions which
could affect the normal operation of the UPS. These conditions do not originate with the UPS, but
may be caused either by the surrounding environment or by the electrical installation (line power side
and load side). A description of the active warning(s) can be viewed by clicking on the yellow triangle
or using the Status button at the bottom of the page.
Fault Indicator—When the red circle with white cross appears, immediate attention should be
given to the severity of the alarm, and service should be called promptly. A description of the active
alarm(s) can be viewed by clicking on the Status button at the bottom of the page.
Regardless of which indicator is active, all available diagnostic information on the unit can be
displayed by touching this area.
Control Buttons: Start Inverter and Stop Inverter—The touchscreen display features two
buttons for starting and shutting down the inverter. The start/stop control incorporates a safety
feature for preventing accidental operation. When the start or stop function for the inverter is
selected, a pop-up window appears asking for confirmation of the action.
Reset Fault—Reset faults (becomes red when there is a system fault).
Alarm Silence—Silence the buzzer in the case of an alarm.
NOTE
If screen is inactive for 30 seconds, the LCD will revert to this page.
BFB
UPS Module
To DC Supply
Module Rectifier
AC Input
Module Bypass
AC Input
UPS Output
DC
Bus
Critical
Load