3.3 Manage UPS Adapter
ManageUPS NET Adapter III offers an open approach to network power management by delivering a
complete set of manageability options including: WEB, Telne and Out-Of-Band accessibility, in
addition to the full-featured, embedded SNMP agent. Event messages are also available as e-mail and
SNMP Traps - a truly versatile tool for managing Liebert NX UPS systems in a network environment.
The software features:
DHCP Network Configuration—Supports automatic IP settings configuration using the
DHCP protocol. The DHCP server must be located on a network that is accessible from the LAN
that ManageUPS-II is connected to.
Multiple Network Access Methods—Site power and UPS status information can be accessed
securely from any computer on your network. View UPS system status in real time for situational
decision support. Access via Telnet, SNMP, or Web Browser. SNMP Agent conforms to RFC1628
Standard UPS MIB.
Network Shutdown—ManageUPS includes a UPS status server and a network shutdown
controller. Use these features with host shutdown software (RCCMD, MopUPS NSA, MopUPS
Professional or MopUPS P/R) to ensure safe shutdown of multiple servers, workstations or PCs in
TCP/IP network environments.
Event and Data Logging—ManageUPS II keeps a log file of UPS events and environment data.
On-board log file viewer lets you filter records for easy analysis.
For details, see http://connectivity.Emersonpower.com/
3.4 Connectivity
Table 3 gives details of the various combinations of connectivity solutions that can be used with the
Liebert NX. Only one of the combinations may be used at a time. Other combinations may be possible.
For further information, see http://connectivity.Emersonpower.com/ The following interfaces can
be found on the Liebert NX:
Table 3 Connectivity combinations
Interface Description Input/Output/Serial/CAN
XS3
Slot available for use with a connectivity option, typically ManageUPS
NET III Adapter
Serial
XS6 Slot for the LIFE.net slot modem Serial
X3
Standard serial interface RS232 COM - female –
Available, if XS3 slot is empty or MUN III card is installed
Serial
X6
Standard serial interface RS-232 COM for external LIFE.net kit (e.g.
LIFE.net, GSM modem) only is XS6 is empty - male - Not available, if a
XS6 slot modem is installed
Serial
X19 2x15-pole screw connector for parallel UPS connection
X20 RJ45 interface for synchronization with external signal
TB1
16-pole screw connector for input contacts (see 3.4.1 - Available
Selectable Input Contacts)
Input
TB2
16-pole screw connector for output contacts (see 3.4.2 - Available
Selectable Output Contacts)
Output
XT 3/8 4-pole screw for EPO input and output Input and Output
XT1 External battery temperature sensor connection Input
TB3 Battery Interface and SKRU Key Status Input and Output
TB4 SKRU Enable Status Input and Output