Emerson NX Power Supply User Manual


 
Operation
Liebert
®
NX
20
2.5.3 Load Transfer and Retransfer-Single Module System
Changing the load from the UPS system to the UPS bypass is called a transfer. Changing the load
from UPS bypass to the UPS system is called a retransfer. Note that the UPS system control logic can
initiate automatic load transfers and retransfers. Refer to 2.6 - Automatic Operations.
Transfer Procedure
1. Press the “Stop Inverter” menu button on the touchscreen.
2. The load will transfer to Bypass mode and Inverter will turn Off.
Retransfer Procedure
1. Press the “Start Inverter” menu button on the touchscreen.
2. The Inverter will synchronize with the bypass and transfer the load to Normal mode.
2.5.4 Maintenance Bypass Load Transfers-Single Module System: If Load is on UPS Bypass
Follow these instructions to manually transfer the load between the Maintenance Bypass and the UPS
bypass line. Do not transfer the load between the Maintenance Bypass and the UPS module (inverter)
output. Use the Monitor/Mimic Display screen to verify that the UPS bypass line is available.
NOTICE
Risk of improper operation. Can cause equipment damage.
Failing to follow the proper sequence when operating any circuit breaker may cause damage
to the connected equipment. Operating a Maintenance Bypass circuit breaker out of sequence
could cut Off power to the critical load.
NOTICE
Risk of improper operation. Can cause equipment damage.
The UPS system must be on internal bypass before the following procedures are performed or
the MIB or the MBB is operated. Doing so may damage to the UPS and the critical load may
be lost.
1. Transfer the UPS system to bypass (see 2.5.3 - Load Transfer and Retransfer-Single Module
System). The “OK to transfer” lamp on the key-release unit will light.
2. If using a key interlock system:
a. Depress the key-release unit push button, turn the key and remove from key-release unit.
b. Insert the key into the lock for the Maintenance Bypass Breaker (MBB); retract the bolt.
3. Close the Maintenance Bypass Breaker (MBB).
NOTICE
Risk of improper operation sequence. May cause equipment damage.
Failure to close the Maintenance Bypass Breaker (MBB) will interrupt power to the load.
4. Open the Maintenance Isolation Breaker (MIB). The UPS system is now isolated from the critical
load and the load is now on Maintenance Bypass.
5. If using a key interlock system,
a. Remove the key from the lock for the Maintenance Isolation Breaker (MIB).
b. Put the key back in the solenoid.
6. If UPS bypass shutdown is required, open the Bypass Input Breaker (BIB). This breaker is
external to the UPS; it may be in the Maintenance Bypass Cabinet.
NOTE
If the maintenance bypass cabinet or switchboard has any other type of custom interlock, follow
the specific instructions for that interlock system to remove the key.
NOTE
The UPS system is now locked in bypass and cannot be retransferred to the inverter until the
key is reinserted.