Security passwords
There are four role based user accounts for the gateway with varying levels of access. The table
below describes this access.
Each of the initial passwords for the user accounts is default. It is recommended, for security
purposes, that these passwords are changed. The administrator password should be
appropriately noted when changed. If it is lost, please contact Emerson Process Management for
technical support.
To change the User Accounts Passwords:
1. Navigate to System Settings>Users>User Accounts.
2. Set the new password for each role based user account, and confirm.
3. Select Submit.
Note
It is suggested that the default security settings in System Settings>Users>User Accounts be
changed to the local IT best practices or the “Normal” setting after initial login. Strong or
custom settings are available for more robust passwords. For more information on this screen
and others please see the User Interface Terminology Guide (00809-0600-4420).
Time settings
The Gateway is the timekeeper for the WirelessHART network, so it is imperative that the
Gateway's time is accurate for timestamp data to be meaningful. Time settings can be found by
navigating to System Settings>Time.
Role User name Web interface access
Executive exec Read-only access
Operator oper Read-only access
Maintenance maint
Configure HART
®
device settings
Configure Modbus communications
Configure Modbus register mapping
Configure OPC browse tree
Configure Active Advertising
Administrator admin
Includes all maintenance privileges
Configure Ethernet network settings
Configure WirelessHART
®
network settings
Set passwords
Set time settings
Set home page options
Configure custom point pages
Restart applications