Emerson Process Management ControlWave LP Network Card User Manual


 
Product Data Document
420DS-4c
July 19, 2007 - Page 4
Bristol
®
ControlWave
®
LP
Remote Automation Solutions
Website: www.EmersonProcess.com/Remote
‘1’ State Voltage: 90 % of input voltage range
‘0’ State Voltage: 10 % of input voltage range
Bus Access: 16-bits wide
Max Accumulator Value: 65536
Electrical Isolation: 1500 VDC
Surge Suppression: 500Vdc MOV to Chasis 38
VDC MOV across input and to Field Common
Meets ANSI/IEEE C37.90-1978
Terminations: Pluggable, maximum wire size is
16 gauge
Status indication: 4 LED’s (one per point)
ControlWave LP Analog Output Module
(Optional)
Number of Points: 4
Output congurations: 1-5 VDC & 4-20 mA
(Individually congured)
Power Loop: 9 to 30 VDC for 4-20 mA AO 10
to 30 VDC for 1-5 VDC AO
Accuracy: 0.1% of span @ + 25
o
C
0.2% of span @ -20 to 70
o
C
0.3% of span @ -40 to 85
o
C
Common Mode Voltage: 500 VDC (AO ground
to chassis)
Surge Suppression: 16 V Transorb across input
to AO Ground Meets ANSI/IEEE C37.90-1975
Environmental Specications
Operating Temperature: -40
o
C to + 70
o
C
(-40
o
F to + 158
o
F)
Storage Temperature: -40
o
C to + 85
o
C
(-40
o
F to + 185
o
F)
Relative Humidity: 15 – 95 Noncondensing
Vibration: 10-150 Hz at 1.0G
150-2000 Hz at 0.5G
RFI Susceptibility: 3V/M at 80-1000 MHz per
EN50082-2
ControlWave LP Packaging
Physical Size: Mounting Plate is 12.5 inches
high x 8.5 inches wide. Unit is 3.5 inches deep.
1
2
3
4
AI -
AI -
AI +
4 - 20 mA
internally powered
transmitter
AI +
AI In +
AI In -
Two Wire
Transmitter
24
Vdc
AI In -
AI In +
4 - 20 mA
externally powered
transmitter
AI +
AI +
AI -
AI -
Two Wire
Transmitter
1
2
3
4
1
2
3
4
Three Wire
Transmitter
AI In +
AI In -
1 - 5 Vdc
AI for externally
powered
transmitter
24 Vdc
+
_
AI +
AI -
AI +
AI -