Emerson Process Management MICRO Power Supply User Manual


 
Page - 10 PIP-ControlWaveLS
Section 3
SPECIFICATIONS
3.1 OPERATING SPECIFICATIONS
Function: Provides four isolated 24Vdc power output terminal pairs to
power an RTU , a Transmitter and/or a number of non-isolated
I/O (associated with a particular ControlWave RTU.
Output Voltage : Electrically Isolated & Regulated 24Vdc ±5%, no load or full
load
Output Current: 0.2A maximum, power limited to 150% of Max. rated power
Supply Shutdown: Below +9Vdc or +19Vdc (Nominal) for 12V or 24V system
(respectively)
12V System:
Max. ON Switchpoint = 8.8V
Max. OFF Switchpoint = 7.8V
24V System:
Max. ON Switchpoint = 19.7V
Max. OFF Switchpoint = 17.4V
Input Voltage: +9 to +30 Vdc
Input Current: Supply Loading: 24V @ 0.2A
Vin @ +9V Iin Max. = .85A
Vin @ +12V Iin Max. = .58A
Vin @ +24 Iin Max. = .29A
Fusing: 2A Slow Blow (5x20 mm) Fuse for 12V/24V System
Electrical Isolation: 500Vdc (Transformer Coupled)
Surge Suppression: 500Vdc (MOV between 24V return and CHASSIS)
30V Transient Suppressor across VIN(9-30V)/GND, 24V/24V
Return – meets ANSI/IEEE C37.90-1978
Terminations: Fixed, Max. wire size is 16 guage
3.2 ENVIRONMENTAL SPECIFICATIONS
Temperature: Operating Range: -40° to +85°C (-40° to 185°F)
Storage Range: -40°to +85°C (-40°to 185°F)
Relative Humidity: 15% to 95% (Non-condensing)