4.4 UPS Output Rating Details
a. VERIFY THE LOAD TO BE CONNECTED DOES NOT EXCEED THE UPS OUTPUT
RATING for the single or combined paralleled UPS units.
(1) FN3KRM-2TXI Not N+1 Hardwire, 120/240Vac, 2,100W, split-phase, 3 wire plus ground
(2) FN3KRM-2TXI Not N+1 4,200W
N+1 2,100W
(3) FN3KRM-2TXI Not N+1 6,300W
N+1 4,200W
(4) FN3KRM-2TXI Not N+1 8,400W
N+1 6,300W
1) FN4KRM-2TXI Not N+1 Hardwire, 120/240Vac, 2,800W, split-phase, 3 wire plus ground
(2) FN4KRM-2TXI Not N+1 5,600W
N+1 2,800W
(3) FN4KRM-2TXI Not N+1 8,400W
N+1 5,600W
(4) FN4KRM-2TXI Not N+1 11,200W
N+1 8,400W
(1) FN5KRM-2TXI Not N+1 Hardwire, 120/240Vac, 3,500W, split-phase, 3 wire plus ground
(2) FN5KRM-2TXI Not N+1 7,000W
N+1 3,500W
(3) FN5KRM-2TXI Not N+1 10,500W
N+1 7,000W
(4) FN5KRM-2TXI Not N+1 14,000W
N+1 10,500W
(1) FN6KRM-2TXI Not N+1 Hardwire, 120/240Vac, 4,200W, split-phase, 3 wire plus ground
(2) FN6KRM-2TXI Not N+1 8,400W
N+1 4,200W
(3) FN6KRM-2TXI Not N+1 12,600W
N+1 8,400W
(4) FN6KRM-2TXI Not N+1 16,800W
N+1 12,600W
4.5 FN Rackmount System Rear Panel Overview
11