Falcon FN6KRM-2TXI Power Supply User Manual


 
4.4 UPS Output Rating Details
a. VERIFY THE LOAD TO BE CONNECTED DOES NOT EXCEED THE UPS OUTPUT
RATING for the single or combined paralleled UPS units.
(1) FN3KRM-2TXI Not N+1 Hardwire, 120/240Vac, 2,100W, split-phase, 3 wire plus ground
(2) FN3KRM-2TXI Not N+1 4,200W
N+1 2,100W
(3) FN3KRM-2TXI Not N+1 6,300W
N+1 4,200W
(4) FN3KRM-2TXI Not N+1 8,400W
N+1 6,300W
1) FN4KRM-2TXI Not N+1 Hardwire, 120/240Vac, 2,800W, split-phase, 3 wire plus ground
(2) FN4KRM-2TXI Not N+1 5,600W
N+1 2,800W
(3) FN4KRM-2TXI Not N+1 8,400W
N+1 5,600W
(4) FN4KRM-2TXI Not N+1 11,200W
N+1 8,400W
(1) FN5KRM-2TXI Not N+1 Hardwire, 120/240Vac, 3,500W, split-phase, 3 wire plus ground
(2) FN5KRM-2TXI Not N+1 7,000W
N+1 3,500W
(3) FN5KRM-2TXI Not N+1 10,500W
N+1 7,000W
(4) FN5KRM-2TXI Not N+1 14,000W
N+1 10,500W
(1) FN6KRM-2TXI Not N+1 Hardwire, 120/240Vac, 4,200W, split-phase, 3 wire plus ground
(2) FN6KRM-2TXI Not N+1 8,400W
N+1 4,200W
(3) FN6KRM-2TXI Not N+1 12,600W
N+1 8,400W
(4) FN6KRM-2TXI Not N+1 16,800W
N+1 12,600W
4.5 FN Rackmount System Rear Panel Overview
11