4.0 PRE-INSTALLATION DETAILS
Falcon Electric, Inc. is not responsible for shipping damage or for filing shipping damage claims. Visually
inspect the equipment for freight damage. If any equipment has been damaged during shipment, retain the
shipping pallet and packing materials for inspection by the carrier, and immediately file a claim for “shipping
damage” with the carrier. If you discover damage after acceptance, file a claim for “concealed damage”.
To file a claim for shipping damage or concealed damage:
a. YOU MUST file with the carrier within 15 days of receipt of the equipment;
b. YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.
WARNING
The UPS, Transformer and Battery Modules are very heavy. Use the proper lifting equipment and take the
proper precautions when lifting or moving them.
1. Always install the FN system indoors in a controlled environment.
2. Install the FN modules in a location with unrestricted airflow around the front and rear sides of the modules,
away from water, flammable liquids, gases, corrosive, and conductive contaminants.
3. Maintain a minimum clearance of 4 inches in the front and rear of the UPS.
4. Maintain an ambient temperature range of 32ºF to 104ºF (0ºC to 40ºC). To assure the maximum life of the
batteries, operation in an ambient temperature of 68ºF to 77ºF (20ºC to 25ºC) is recommended.
OPERATION IN TEMPERATURES ABOVE 77ºF (25ºC) WILL REDUCE BATTERY LIFE.
5. The FN Series Rackmount system modules must be installed in a standard 19” equipment rack having hard
mounted shelves under the modules to properly support their weight.
6. When selecting a suitable rack location for the UPS, Transformer and battery bank(s) always verify the
floor loading capabilities:
4.1 Floor Loading Requirements
a. VERIFY THE FLOOR OR SUPPORTING SURFACE UNDER THE EQUIPMENT RACK IS RATED TO SUPPORT
THE WEIGHT OF THE TOTAL WEIGHT OF THE RACK, THE FN MODULES AND ALL OTHER EQUIPMENT INSIDE
THE RACK.
UPS Module:
(1) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 53 lbs. (24 kg)
(2) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 106 lbs. (48 kg)
(3) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 159 lbs. (72 kg)
(4) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 212 lbs. (96 kg)
Battery Bank Modules (for all FN Rackmount models)
(1) FNBRM-1S7 = 150 lbs. (68 kg)
(2) FNBRM-1S7 = 300 lbs. (136 kg)
(3) FNBRM-1S7 = 450 lbs. (204 kg)
(4) FNBRM-1S7 = 600 lbs. (272 kg)
Output Transformer Module (for all FN Rackmount models)
(1) FNITRM-2 = 91 lbs. (41 kg)
(2) FNITRM-2= 181 lbs. (82 kg)
(3) FNITRM-2= 272 lbs. (123 kg)
(4) FNITRM-2= 362 lbs. (164 kg)