5.4 LCD Display Overview
LCD Display
5.5 LCD Icon Descriptions
1. Bypass input is out of tolerance, UPS failed to transfer to bypass, or bypass input is out of
tolerance when the UPS is in Economy/Green Mode.
2. Utility loss or the utility input is out of tolerance.
3. UPS lost inverter output and transferred to bypass.
4. Battery voltage is out of tolerance, or defective batteries.
5. The UPS output is overloaded.
6. The UPS is presently in maintenance mode.
7. MIMIC Display showing Line, UPS, Battery and Load. When referenced in conjunction with arrows
8, 9 and 11, it defines the operational state of the UPS. They also indicate the source of the
input/output/battery parameter readings displayed on the Measurement Display (12).
8, 9 & 11. MIMIC display and Measurement location indicators.
10. Battery and Low Battery Icons
. The battery icon is displayed as part of the MIMIC display.
In the event of a utility loss that depletes that battery charge, the Low Battery icon is displayed
until the batteries have recharged to a reasonable level. In the event of a complete battery discharge,
the low battery icon will be displayed along with an audible alarm. When the batteries have recharged
to a reasonable level, the normal battery icon will be displayed.
12. Measurement Display. The Measurement display is used to show the input/output/battery readings,
program mode settings, status and error codes.
5.6 Status and Error Code Descriptions
OFF or BPS-- Displayed when the UPS is turned off with the “Off” button, EPO or remote shutdown.
EPO -- When an optional EPO communications board is installed, EPO is displayed alternately with
the OFF or BPS message, after an EPO signal has been applied to the EPO interface
connector. After an EPO condition, the UPS input circuit breaker must be turned off and the
“Off” button must be depressed twice for 5 seconds to reset the UPS prior to turning the UPS
and Bypass input circuit breakers back on.
17
Shown in Test Mode