5.3. Server Side Map Descriptors
5.3.1. FieldServer Specific Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name
Name of this Map Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where data
is to be stored in the FieldServer
One of the Data Array names
from “Data Array” section above
Data_Array_Offset Starting location in Data Array
0 to maximum specified in “Data
Array” section above
Function
Function of Server Map
Descriptor
Server
5.3.2. Driver Specific Map Descriptor Parameters
Column Title Function Legal Values
Node_Name
Name of Node to fetch
data from
One of the Node names specified in
“Client Node Descriptor” above
Address_Type = ADU
Coil, Discrete_Input, Input_Register,
Holding_Register, Single_Coil,
Single_Register
Address_Type = PDU
FC01, FC02, FC03, FC04,
FC05, FC06, FC15, FC16
Address_Type = Modicon_5digit
Data_Type
8
Specify memory area
- (Dash), Single_Register, Single_Coil
Length
Length of Map
Descriptor
1-10000.
Address_Type = ADU
1-65536
Address_Type = PDU
0-65535
Address_Type = Modicon_5digit
Address
Starting address of
read block
40001, 30001, etc
Data_Array_Low_Scale*
Scaling zero in Data
Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 0
Data_Array_High_Scale*
Scaling max in Data
Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 100
Node_Low_Scale*
Scaling zero in
Connected Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 0
Node_High_Scale*
Scaling max in
Connected Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647. 100
Node_Offline_Response
Set the FieldServer
response to the
Modbus RTU Client
when the Server Node
supplying the data has
gone offline
No_Response,
Old_Data,
Zero_Data,
FFFF_Data,
Refer to Appendix A.6 for further
information.
8