Appendix A.2. Malfunction Table
When an event is reported in the Incident Report (QIR) then the driver compares the event
description to text in the table below. If the text matches an an entry in the ‘Malfunction’
column (and is preceeded by the string MALFUNC) then the Data Array element at the
specified offset is set to 1. If the text matches the ‘Return to Normal’ text then the
malfunction is considered as cleared and the Data Array element is set to zero.
The Data Array elements are all set to zero when
Event 19 reports ” ALARM RESET “ or Event 37 reports “ALL MALFUNCTIONS CLEAR”
The Malunction text strings generated by the TGM unit are not the same for all units. They
can be customized in theTGM’s config.dat file. For this reason, this driver allows the strings
in the table below to be customized too – see Appendix B.5. In addition to allowing this
table to be customised in the configuration file, the driver can use a config.dat file to directly
customise the table – see Appendix B.7
Offset Malfunction Return to Normal
20 BASELINE OUT OF RANGE BASELINE BACK TO NORMAL
22 IGNITER SWITCH IS ON IGNITER SWITCH IS OFF
24 FLAME IGNITION DISABLED FLAME IGNITION ENABLED
26 LOW VACUUM VACUUM BACK TO NORMAL
28 FLAMEOUT RESTART FLAMEOUT BACK TO NORMAL
30 LINE LEAK TEST MALFUN LINE LEAK BACK TO NORMAL
32 POWER FAILURE POWER RESTORED
38 FAILED TO LOAD PROGRAM
39 DPM TIMEOUT DPM BACK TO NORMAL
41 RELAY FILE ERROR OPERATIONS CHECK DONE
45 CHECK I/O AND FUSES I/O AND FUSES OK NOW
47 TGM IN DEBUG MODE
48 DISK NEARLY FULL ADEQUATE DISK STORAGE NOW
50 FLAMEOUT CONDITION RETURN FROM FLAMEOUT
52 FAILED FLAME TEST FLAME TEST OK NOW
54 FAILED RESPONSE TEST RESPONSE TEST OK NOW
56 FAILED BLOCK LEAK CHECK BLOCK LEAK CHECK OK NOW
58 ANALOG SUBSYSTEM FAILURE ANALOG SUBSYSTEM NORMAL
60 ANALOG CHANNEL FAILURE ANALOG CHANNEL NORMAL
62 PRINTER OFF LINE PRINTER BACK TO NORMAL
64 REMOTE OFF LINE REMOTE BACK TO NORMAL
66 DISK READ/WRITE ERR DISK BACK TO NORMAL
68 LAN READ/WRITE ERROR LAN BACK TO NORMAL
70 DISK FULL - DATA LOST DISK NO LONGER FULL
75 HIGH SAMPLE VARIANCE SAMPLE VARIANCE OK NOW
80 COUS SENSOR TIMEOUT COUS TIMEOUT CORRECTED
82 COUS GETTER INOPERATIVE COUS GETTER OK NOW
84 ACOUSTIC SENSOR FAILURE ACOUSTIC SENSOR RECOVERD
86 GETTER TEMPERATURE LOW GETTER TEMPERATUR OK NOW
88 LOW SAMPLE FLOW SAMPLE FLOW OK NOW
90 TGM HYDROGEN LEAK HYDROGEN LEAK REPAIRED