FieldServer FS-8700-103 Computer Drive User Manual


 
FS-8700-103_ATMI_TGM_Serial Manual Page 23 of 28
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Message
Notes and Corrective Action
TGM: #10 Err. No space. Reject
Gas Name=<%s> Index
Value=%d
An attempt has been made to extend the gas name table.
There is insufficient space to add more names. Remove this
entry from the configuration CSV file
3
.
TGM: #11 FYI. User added Gas
Name=<%s> Index Value=%d
This message may be ignored. It is printed to alert you to
the fact that the driver has updated the Gas Name table by
adding a new gas name and index value. Ensure that index
values are unique.
TGM: #12 FYI. Duplicate Gas
Units=<%s>. Value has been
updated from=%d to=%d
This message may be ignored. It is printed to alert you to
the fact that the driver has updated the Gas Engineering
Unit table so that default values have been modified.
TGM: #13 Err. No space. Reject
Gas Units=<%s> Index
Value=%d
An attempt has been made to extend the Fas Engineering
Units table. There is insufficient space to add more names.
Remove this entry from the configuration CSV file.
3
TGM: #14 FYI. User added Gas
Units=<%s> Index Value=%d
This message may be ignored. It is printed to alert you to
the fact that the driver has updated the Gas Engineering
Units Table by adding a new gas name and index value.
Ensure that index values are unique.
TGM: #15 FYI. Duplicate
Malfunction=<%s>. Index Val
has been updated from=%d
to=%d
This message may be ignored. It is printed to alert you to
the fact that the driver has updated the Malfunction Table so
that default values have been modified. Ensure that the
index value is less than 100.
TGM: #16 Err. No space. Reject
Malfunction=<%s> Index
Val=%d
An attempt has been made to extend the Malfunction Table.
There is insufficient space to add more names. Remove this
entry from the configuration CSV file.
3
TGM: #17 FYI. User added
Malfunction=<%s> Index
Val=%d
This message may be ignored. It is printed to alert you to
the fact that the driver has updated the Malfunction Table by
adding a new gas name and index value. Ensure that index
values are unique and that the index value is less than 100.
TGM: #18 FYI. Duplicate
Normal Event=<%s>.
Index Val has been updated
from=%d to=%d
This message may be ignored. It is printed to alert you to
the fact that the driver has updated the ‘Return to Normal’
Table so that default values have been modified. Ensure
that the index value is less than 100.
TGM: #19 Err. No space. Reject
Normal Event=<%s> Index
Val=%d
An attempt has been made to extend the ‘Return to Normal’
Table. There is insufficient space to add more names.
Remove this entry from the configuration CSV file.
3
TGM: #20 FYI. User added
Normal Event=<%s> Index
Val=%d
This message may be ignored. It is printed to alert you to
the fact that the driver has updated the ‘Return to Normal’
Table by adding a new gas name and index value. Ensure
that index values are unique and that the index value is less
than 100.
3
Modify the configuration CSV file. Download the modified file to the FieldServer and Reset the
FieldServer for the changes to take effect.