FieldServer FS-8700-123 Computer Drive User Manual


 
FS-8700-123_MetOne Particle Counter by Hach Ultra Analytics Manual Page 23 of 26
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@fieldServer.com
Message Description
MET1:#13 Err. Node=%d cant be
selected because not defined in
config.
The reported device could not be selected because there
isnt a node descriptor whose Node_ID matches the
reported device.
4
"Met1:#14 FYI Poll_Delay
overridden to %d
The driver has set the default poll delay to the reported
value. This setting can be overridden in the configuration
file.
4
Met1:#15 Err. Set MD Length=%d
The driver has determined that the Length parameter is
too small. The reported length is the driver suggestion.
4
Met1:#16 Err. Set MD Length
The parameter called Length must be specified for each
Map Descriptor. It tells the FieldServer how much Data
Array space to reserve. Review the Map Descriptor
examples in this manual.
4
MET1:#17 Err. MD too long,
Max=%u
Review the Map Descriptor examples in this manual.
4
MET1:#18 Err. Invalid Port=%d.
Valid Range=0-63
Invalid entry for port.
4
MET1:#19 Err. Invalid
SubDevice=%d. Valid Range=1-
64
Invalis entry for SubDevice
4
MET1:#20 Err. Met1_Function not
specified
MET1:#21 Err.
Met1_Function='%s' not
recognized
The parameter “Met1_Function’ must be specified for
every Map Descriptor. Refer to Section 4.4.2 as well as
Map Descriptor examples provided in Chapter 4.
4
Appendix A.1. Driver Operating and Error Statistics
These notes outline any driver specific use of the normal driver operating stats documented
in the FieldServer Configuration Manual.
Timeouts : During normal polling, a timeout can mean that the field device did not
respond to the select message, (or the sub-device select message) or did not respond to
the poll for data or the command poll.
Exception Stats: If the driver select a device , sub-device or port and the return code
from the device is unexpected the this stat is incrmented by 1.
Ignored Stats: If the current record is read and there is more data than can be stored
than specified by the Length of the Map Descritor then this stat is incremented.
The driver does not use the normal operating stats to count message and bytes received
in response to select / sub select messages.
4
Update the configuration file, download the modified configuration file and reset the FieldServer for the
changes to take effect