ProtoNode Driver Manual (FS-8700-124) rev 6.doc Manual
Page 7 of 17
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web:www.protocessor.com
Tel: 408.964.4433 Fax: 408.964.4425 Toll_Free: 800.317.8319 email: sales@protocessor.com
4.2. Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device
is connected to the ProtoNode
P1-P8
Protocol
Specify protocol used
TOSHIBA_UPS, TOSH_UPS
Baud*
Specify baud rate
1200–9600, standard baud rates
only (Vendor limitation)
Parity*
Specify parity
Even
Data_Bits*
Specify data bits
7
Stop_Bits*
Specify stop bits
1
Handshaking*
Specify hardware handshaking
None
Poll _Delay*
Time between internal polls
0-32000 seconds, 0.05 seconds
Example
// Client Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Handshaking,
Data_Bits
Poll_Delay
P1,
TOSH_UPS,
1200,
Even,
None,
7
0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric characters
Node_ID
Modbus station address of
physical server node
1
Protocol
Specify protocol used
TOSH_UPS, TOSHIBA_UPS
Node_Type
The model of the TIC UPS
1600, 1800, 4200, G8000,
G8000MM, G9000
Connection
Specify which port the device is
connected to the ProtoNode
P1-P8
1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for
details of the ports available on specific hardware.