FieldServer FS-8700-124 Power Supply User Manual


 
ProtoNode Driver Manual (FS-8700-124) rev 6.doc Manual
Page 8 of 17
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web:www.protocessor.com
Tel: 408.964.4433 Fax: 408.964.4425 Toll_Free: 800.317.8319 email: sales@protocessor.com
Example
// Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Node_Type,
Connection
PLC 1,
1,
TOSH_UPS,
1600,
P1
4.4. Client Side Map Descriptors
4.4.1. FieldServer Related Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where
data is to be stored in the
FieldServer
One of the Data Array names
from “Data Array” section
above
Data_Array_Offset
Starting location in Data
Array
0 to maximum specified in
Data Array” section above
Function
Function of Client Map
Descriptor
RDBC, WRBC, WRBX
4.4.2. Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch
data from
One of the node names specified in
“Client Node Descriptor” above
Toshiba_Command
Type of information
on UPS
OV1, OV2, OV3 etc (Appendix A)
Length
Length of Map
Descriptor
1 All value commands
24 All bit commands