5.4.3. Map Descriptor Example.
Map_Descriptor_Name, Scan_Interval, Data_Array_Name,
Data_Array_Offset,
Function, Node_Name, Secutron_Type, Secutron_Circuit, Length
P1c1_devices, -, P1c1_devices 0, Server, Node_1, device, 1, 200
P1c1_function, -, P1c1_function 0, Server, Node_1, function, 1, 200
P1c69_restart, -, P1c69_restart, 0, Server, Node_1, device, 69, 100
P1c69_function, -, P1c69_function, 0, Server, Node_1, function, 69, 100
P1c90_reset, -, P1c90_reset, 0, Server, Node_1, device, 90, 100
P1c90_function, -, P1c90_function, 0, Server, Node_1, function, 90, 100
Any unique
name.
Name will
appear in
Bridge Map
Descriptor
status
information
screens.
The rate at which
the driver polls the
panel.
A Data Array name
must be one found
under Data_Arrays.
Data from a circuit
event will be stored
in the array at
Data_Array_Offset.
Function may not
be read or write
since it
implements a
Server. Function
may only be
Server.
A name given
to the device
to which the
FieldServer is
connected.
The type of data
the Map
Descriptor points
to. Device data
contains alarm
statuses. Function
data contains
condition codes.
Refer to Appendix
A.1 for more
information.
The circuit or
zone number
used to trap
incoming events
into the Map
Descriptor. See
Driver notes.
The number of
devices on the
circuit this Map
Descriptor can
detect for incoming
events.