FieldServer FS-8700-72 Network Router User Manual


 
FS-8700-72 Secutron Manual Page 9 of 15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: support@fieldserver.com
5. Configuring the FieldServer as a Secutron Modul-R driver Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration
Manual. The information that follows describes how to expand upon the factory defaults provided in the
configuration files included with the FieldServer (See “.csv” files provided with the FieldServer).
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order
to enable the FieldServer for Secutron Modul-R driver communications, the driver independent
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) need
to be declared in the “Server Side Nodes” section, and the data to be provided to the Client needs to be
mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1. Data Arrays
Section Title
Data_Arrays
Column Title Function Legal Values
Data_Array_Name Provide name for Data Array
Up to 15 alphanumeric
characters
Data_Format
Provide data format. Each Data Array
can only take on one format.
Bit, Packed_Bit, Byte,
Uint16
Data_Array_Length
Number of Data Objects. Must be larger
than the data storage area required for
the data being placed in this array.
1-10,000
Example
// Data Arrays
Data_Arrays
Data_Array_Name, Data_Array_Format, Data_Array_Length
p1c1_devices, Bit, 1
p1c1_function, Byte, 1000
p1c69_restart, Bit, 1000
p1c69_function, Byte, 100
p1c90_reset, Bit, 100
p1c90_function, Byte, 100