FieldServer FS-8700-73 Computer Drive User Manual


 
FS-8700-73 BACnet MSTP Driver Manual Page 8 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com
4.3. Client Side Connection Descriptions
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is connected to the
FieldServer
P1-P8
3
, R1-R2
4
Baud Specify baud rate
9600, 38400,
76800
5
Parity* Specify parity
Odd, Even, None
Data_Bits* Specify data bits
7, 8
Stop_Bits* Specify stop bits
1,2
Protocol Specify protocol used BACnet_MSTP
Poll Delay* Time between internal polls
0-32000s, 1s
Timeout Application logger timeout 30s
Max_Master**
Specify the highest possible MAC_Address that exists on
the MSTP network. (See Appendix C.1)
1-127
Max_Info_Frames
Specify the maximum number of information frames the
connection may send before it must pass the token.
1-65535
Example
// Client Side Connections
Connections
Port,
Baud, Parity, Data_Bits,
Stop_Bits,
Protocol, Poll_Delay Timeout
R1, 38400,
None, 8, 1, BACnet_MSTP,
0.100s 30s
3
P
1
to P
8
will require the optional RS-485 converter (Part # 4301-00)
4
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
5
76800 baud is supported on the X30, X25 and ProtoCessor