FieldServer FS-8700-73 Computer Drive User Manual


 
FS-8700-73 BACnet MSTP Driver Manual Page 9 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com
4.4. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID Specify the BACnet Device object instance.
6
1 - 4194303
Protocol Specify protocol used BACnet_MSTP
Port Specify port P1-P8
7
, R1-R2
8
MAC_Address MAC_Address of the physical server node.
6
1-127 (for Master
Nodes)
1-254 (for Slave
Nodes)
Network_Number*
Use this parameter if the remote MSTP server device
is on another BACnet network connected via a router.
1,2,3.... 16 bit positive
numbers.
5
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port
BCU_1, 1, BACnet_MSTP, R1
6
Either Node_ID OR MAC_Adddress must be specified. If the Server Node supports Who-Is and I-Am
then it is better to use the Node_ID parameter.
7
P
1
to P
8
will require the optional RS-485 converter (Part # 4301-00)
8
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.