g
GE
OPM_SGS_USM_10K_40K_0US_V010.doc 51/88 Operating Manual
SG Series
10, 20, 30 & 40 kVA
7.2.3 Restore to normal operation after “total off”
View of the panel after pressing the
button “total off”.
• All Contacts are open;
• Rectifier, Inverter and Static-Switch
shutdown.
1. Reset “total off” by pressing and
holding the “total off” button and the
“
inverter on
”
( I )
key simultaneously
until the Rectifier starts.
2. Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case
of External Battery.
3. Press
“
inverter on
”
( I ) key
.
• Soft-start of Inverter indicated with
blinking LED.
• At the end of Soft-start the LED
remains lit.
• UPS output LED indicates Load on
Inverter.
The LCD must display on the main screen the status “LOAD ON INVERTER”.
End of procedure