GenTran 2026 Switch User Manual


 
Installation and Operating Instructions
GENERATOR SAFETY TRANSFER SWITCH MODELS 2026, 3028
Thank you for purchasing a GenTran
®
Manual Transfer Switch designed to
safely connect a portable generator to the load center in your home or
business (single phase only) for standby power applications. Product features
include:
Generator and Utility feeds mechanically interlocked to prevent dangerous
utility or generator back feeding – thereby avoiding property damage and
serious injury to electrical workers.
Pre wired for fast, easy connection to the load center
Each model can be expanded to up to 10 circuits using interchangeable type
circuit breakers – so as your needs change, just expand it!
Accommodates GFCI and Arc-Fault breakers to meet the latest NEC
requirements.
Dual wattmeters are provided to help you monitor and balance the loads on
your generator, prolonging generator life
Flexible generator connections – Use the Power Inlet for a quick cord
connection to your generator, or ask your contractor to hardwire your
generator connection.
Surface or Flush Mounting (with flush mounting plate sold separately).
Warning: Gen/Tran transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and
experienced in working with generators. Gen/Tran accepts no responsibility for accidents, damages or personal injury caused by
incorrect installation. These transfer switches are intended for surface mounting INDOORS only. GenTran transfer switches are UL
listed to UL Standard 1008 and meet the criteria of National Electrical code Article 702.6 for Optional Standby Systems.
Caution: If using the generator and transfer switch for larger appliances, such as electric water heaters, clothes dryers, electric ranges
and small air conditioners, check the labels on the appliances to be sure they do NOT exceed the rating of the generator. No
appliance should have an amperage rating that exceeds the individual breaker rating in the transfer switch (20 or 30 amps).
Model: 2026 3028
# Circuits Provided 6 8
Max # Circuits 10 10
REQUIRED BREAKER FOR MAIN LOAD CENTER
(not included in this kit)
60 amp 2-pole 60 amp 2-pole
Breakers Provided with Unit 2 – 15 amp 1-pole
2 – 20 amp 1-pole
1 – 20 amp 2-pole
2 – 15 amp 1-pole
2 – 20 amp 1-pole
1 – 20 amp 2-pole
1 – 30 amp 2-pole
Max GEN Watts 5000 7500
Max GEN Amps 20 Amps 30 Amps
Voltage 120/240 Volts 120/240 Volts
NEMA Type Enclosure 1 – Indoor Only 1 – Indoor Only
NEMA Configuration of Male Inlet L14-20 L14-30
Phase 1 1
Minimum Gauge Cord Size 12/4 10/4
Tools Needed for Installation:
Power Drill
Wire Stripper and cutter
Screw drivers
Tape measure
Wall anchors and screws
Other supplies needed if hardwiring to a Power Inlet
Box include Romex, ½” connector, and wire connectors
2-pole 60 amp breaker for main panel