HP (Hewlett-Packard) 380976 Power Supply User Manual


 
380976 V3.1 6/08
10
3Φ 4-Wire KW, HP, KVA, KVAR, Power Factor & Phase Angle Measurement
1.
First, measure W
R(L1)
(refer to the diagram below).
a. Set the rotary switch to the “
V ” position.
b. Press and hold the “RANGE” key while setting the rotary switch to the “KW/KVA”
position, the 3
φ
4W and W
L1
symbols should appear.
c. Insert the test leads into the input jacks.
d. Connect the neutral line to the COM (black) terminal.
e. Connect the test probe of the V (red) terminal to the first phase (e.g. R or L1).
f. Clamp on to the same phase (e.g. R or L1).
g. The power clamp meter will automatically select the proper range.
h. Wait until the reading is stable (about 6 seconds) and then press the “HOLD” key;
the W
L1
symbol will clear and the W
L2
symbol will appear in order to instruct users
to take the W
S(L2)
measurement.
2.
Second, measure W
S(L2)
(refer to the diagram that follows the steps below)
a. Disconnect the test probe from the phase where the jaw was clamped in the
previous measurement.
b. Connect the test probe of the V (red) terminal to the second phase (e.g. S or L2).
c. Clamp on to the phase where the test probe is connected (e.g. S or L2 phase)
d. The power clamp will automatically select proper range.
e. Wait until the reading is stable (about 6 seconds) and then press the “HOLD” key;
the W
L2
symbol will disappear. The W
L3
symbol will appear to instruct users to take
the W
T(L3)
measurement.