HP (Hewlett-Packard) AF074A Server User Manual


 
About this guide 7
About this guide
Rack options installation guide
This installation guide includes the instructions for installing rack option kits that are compatible with the HP
10000 G2 Series Rack.
For more information, see the HP 10000 G2 Series Rack User Guide on the HP website
(http://www.hp.com/go/rackandpower).
Important safety information
WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that:
The rear leveling feet are extended to the floor.
The full weight of the rack rests on the rear leveling feet and front stabilizer feet.
WARNING: To reduce the risk of personal injury or damage to the rack and equipment, the
racks must be positioned and secured together according to these instructions. Failure to do so
could result in an unstable installation.
WARNING: Components can be very heavy. To reduce the risk of personal injury or damage to
the equipment:
Remove all pluggable power supplies and modules to reduce the weight of the product before
lifting it.
Observe local occupational health and safety requirements and guidelines for manual
material handling.
Get help to lift and stabilize the product during installation or removal, especially when the
product is not fastened to the rails. When the component weighs more than 22.5 kg (50 lb),
at least two people must lift the component into the rack together. If the component is loaded
into the rack above chest level, a third person must assist in aligning the rails while the other
two support the component.
Use caution when installing the component in or removing the component from the rack; it is
unstable when not fastened to the rails.
Additional rack considerations
Consider the following specifications and components, with regard to your specific rack configuration:
PowerIf a UPS is installed, do not exceed its output rating. Be sure to review the installation
instructions provided with each component for important cautions and warnings.
PDUsInstall PDUs before installing other components.
HeightThe height of the rack and of rack-mountable components is measured in U increments, where
U = 4.5 cm (1.75 in). When you are configuring your rack installation, remember that the total U
measurement of the components you want to install cannot exceed the stated U height of the rack.