HP (Hewlett-Packard) DL760 Server User Manual


 
System Unit
System UnitSystem Unit
System Unit
Dimensions
Dimensions Dimensions
Dimensions
(HxWxD)
12.14 x 17.5 x 27 in (30.83 x 44.45 x 68.58 cm)
Weight
WeightWeight
Weight
165 lb (75 kg)
No hard drives installed,
two power supplies
Input Requirements (per
Input Requirements (perInput Requirements (per
Input Requirements (per
power supply)
power supply)power supply)
power supply)
Rated Input Voltage
100 to 120 VAC/200 to 240 VAC (lowline/highline)
Rated Input Frequency
47 to 63 Hz (lowline/highline)
Input Power
740W/1700W (lowlinehighline)
Rated Input Current
8A at 100 VAC/10A at 200 VAC (lowlinehighline)
BTU Rating
BTU RatingBTU Rating
BTU Rating
(Maximum output)
(
NOTE
NOTENOTE
NOTE
that the maximum heat
output by the server is equal to
the electrical power input.)
1555 Watts [5309 BTU/hr]
(System is configured to draw
maximum power)
SCSI Connector
SCSI ConnectorSCSI Connector
SCSI Connector
One VHDCI connector for tape
support only
Power Supply Output
Power Supply OutputPower Supply Output
Power Supply Output
Power (per power supply)
Rated Steady-State Power
500W/1150W (lowlinehighline)
Maximum Peak Power
540W/1150W (lowlinehighline)
Temperature Range
Temperature RangeTemperature Range
Temperature Range
Operating
50° to 95° F at sea level, altitude de-rating of 1.8° F per
1,000 ft to 10,000 ft (10° to 35° C at sea level, altitude
de-rating of 1° C per 300 m to 3,000 m). Maximum rate
of change is 18° F/Hr (10° C/Hr)
Non-operating
22° to 140 ° F ( -30° to 60° C). Maximum rate of change
is 36° F/Hr (20° C/Hr)
Relative Humidity
Relative HumidityRelative Humidity
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity, 82.4° F (28° C) maximum
wet bulb temperature, non-condensing
Non-operating
5 to 95% relative humidity, 101.7° F (38.7° C) maximum
wet bulb temperature, non-condensing
Maximum Wet Bulb
Maximum Wet BulbMaximum Wet Bulb
Maximum Wet Bulb
Temperature
TemperatureTemperature
Temperature
101.7° F (38.7° C)
Acoustic Noise
Acoustic NoiseAcoustic Noise
Acoustic Noise
Idle
(Fixed Disk Drives Spinning)
L
L L
L
WAd
WAdWAd
WAd
(BELS)
7.0
L
L L
L
pAm
pAmpAm
pAm
(dBA)
54
Operating
(Random Seeks to Fixed Disks)
L
L L
L
WAd
WAdWAd
WAd
(BELS)
7.0
L
L L
L
pAm
pAmpAm
pAm
(dBA)
54
QuickSpecs
Compaq ProLiant DL760
Compaq ProLiant DL760Compaq ProLiant DL760
Compaq ProLiant DL760
TechSpecs
DA - 10813 North America — Version 39 — October 17, 2003