HP (Hewlett-Packard) H5M59A Power Supply User Manual


 
Hardwired PDU
H5M75A
200-240V
50-63A
46A
11040VA @230V
Terminal block
for hardwired
installation
3 x 20A
30 x IEC C13
6 x IEC C19
5.7kVA Dual
Voltage PDU
H5M63A
200-208V
20A
3 phase WYE
27.7A
5764VA @208 3Ø
8ft(2.4m) cord
with attached
NEMA L21-20P
3 x 20A
20 x IEC C13
3 x NEMA 5-
20R
8.6kVA Dual
Voltage PDU
H5M64A
200-208V
30A
3 phase WYE
41.5A
8646VA @208 3Ø
8ft(2.4m) cord
with attached
NEMA L21-30P
3 x 20A
20 x IEC C13
3 x IEC C19
3 x NEMA 5-
20R
8.6kVA PDU
H5M62A
200-208V
30A
3 phase Delta
41.5A
8646VA @208 3Ø
8ft(2.4m) cord
with attached
NEMA 15-30P
3 x 20A
24 x IEC C13
6 x IEC C19
11kVA PDU
H5M72A
380-415V
16A
3 phase WYE
16A per phase
11084VA
@ 400V 3Ø
8ft(2.4m) cord
with attached
IEC 516P6
3 x 16A
24 x IEC C13
6 x IEC C19
Full Height vertical models
11kVA PDU
H5M73A
380-415V
16A
3 phase WYE
16A per phase
11040VA
@ 400V 3Ø
8ft(2.4m) cord
with attached
IEC 516P6
3 x 16A
36 x IEC C13
6 x IEC C19
11kVA PDU
H5M67A
380-415V
30A
3 phase WYE
24A per phase
11040VA
@400V 3Ø
8ft(2.4m) cord
with attached
IEC 530P6
3 x 20A
36 x IEC C13
6 x IEC C19
480/277 Volt models
13.2kVA PDU
H3X07A
480V 30A 3
phase WYE
16A per phase
13301VA
@480V 3Ø
9.8ft(3M) cord
with attached
IEC 530P7
3 x 20A
15 x LS-26
19.9kVA PDU
H3X08A
480V 30A 3
phase WYE
24A per phase
19952VA
@480V 3Ø
9.8ft(3M) cord
with attached
IEC 530P7
6 x 20A
30 x LS-26
*
NOTE:
HP Basic PDU models H5M56A and H5M57A require an IEC 320-C19 to country specific plug inlet cord which is sold separately.
NOTE:
Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions.
http://www.hp.com/go/powercordmatrix.
Disclaimer:
HP makes no recommendations regarding power connector manufactures. Please consult a licensed professional to
determine the best connector or receptacle for your specific needs.
QuickSpecs
HP Basic Power Distribution Units
Basic PDU Family Information
DA - 14557 North America — Version 7 — October 1, 2013