HP (Hewlett-Packard) Console Management Controller Network Card User Manual


 
Pin Layout Configuration D-3
Table D-1
RJ-12 Pin Layout Specifications
Pin Temperature
sensor
Humidity sensor Discrete
inputs
Smoke sensor Alarm relays
1 Sensor Humidity signal (4mA to
20mA)
Contact of
sensor
3
Contact of sensor Contact NC
1
2 Sensor Ground (4mA to 20mA) Contact of
sensor
3
Contact of sensor Contact C
1
3- - - - Contact NO
1
4- - - - -
5 - Ground - Ground Ground
6 - 24VDC, 44mA 24VDC, 160 mA 24VDC, 160mA
2
Note: 1. The alarm relay contacts are rated for a maximum of 24VDC and 800mA, when connecting to an external
power source.
2. The CMC can supply up to 160mA to users from its internal 24VDC power supply via the two alarm relay
ports. The 160mA can be split as needed between the two ports.
3. Intrusion sensors can be connected to Auxiliary 1 and 2 input ports to allow monitoring additional doors.
Users may also wire a simple switch closure device between pins 1 and 2. Pin 2 is connected to the CMC
signal ground and pin 1 is connected to the CMC signal input. Opening or closing the switch will trigger an