HP (Hewlett-Packard) HP R1500 G3 UPS Power Supply User Manual


 
Maintenance 25
Testing the new battery module
After installing the new battery module, press the Test/Alarm Reset button. For information on initiating a
self-test, see "Initiating a self-test (on page 20)."
IMPORTANT: The UPS does not execute a self-test until the batteries are 90 percent charged.
If the installation has been successful, the UPS enters Operate mode. If the installation has not been
successful, the alarm beeps, the On Battery LED illuminates, and the General Alarm LED flashes. If this occurs,
repeat the procedures in "Replacing the batteries (on page 22)," and check the battery terminal connections.
If the condition persists, see "Troubleshooting (on page 31)."
IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
90% of their capacity within 24 hours
100% of their capacity within 48 hours
Replacing the UPS
To remove the UPS:
1. Power down all attached load devices.
2. Power down the UPS ("Powering down the UPS" on page 21).
3. Unplug the UPS power cord.
4. Disconnect the communications cable.
5. Unplug the load devices.
6. Remove the UPS front bezel ("Removing the UPS front bezel" on page 22).
7. Remove the UPS battery bracket.
8. Remove the UPS battery modules.
9. Remove the screws securing the UPS to the rack.
10. Remove the UPS from the rack.
To replace the component, reverse the removal procedure.
Replacing the UPS option card
This component is hot-swappable and can be replaced without powering down the UPS.
1. (optional) To replace the component with the UPS powered down, refer to "Powering down the UPS (on
page 21)."