HP (Hewlett-Packard) HP R1500 G3 UPS Power Supply User Manual


 
Troubleshooting 31
Troubleshooting
LED and audible alarm troubleshooting
Condition Power On
LED
(green)
On Battery
LED
(yellow)
Overload
LED
(red)
General
Alarm LED
(red)
Audible alarm Can alarm
be silenced
("Silencing
an audible
alarm" on
page
20
)?
UPS operating from
utility
On Off Off Off No audible alarm N/A
Buck mode (high
input voltage)
On Off Off Off No audible alarm N/A
Boost mode (low
input voltage)
On
Off
Off
Off
No audible alarm
N/A
Over temperature
condition
On On Off Flashing OnContinuous No
Battery test failure
Off On Off Flashing OnContinuous Yes
Fan failure
On Off Off Flashing OnContinuous No
Output short circuit
On On On Flashing OnContinuous No
Power up failure from
a DC startLow
battery (no utility
power)
Flashing Flashing Flashing Flashing On3 beeps/10
seconds
No
Low battery (no utility
power)
Off On Off Off On2 second
beep
No
OnlineUPS power
capacity exceeded
On Off On Off On1 second
beep
No
Overload timeout
Off Off On Flashing OnContinuous No
On batteryInput
voltage is out of
range
On On Off Off On2 second
beep
Yes
On batteryNo
utility power
Off On Off Off On4 second
beep
Yes
On battery—Battery
voltage condition
Flashing Off Off Flashing OnContinuous Yes
On
battery—Overload
condition
Off
On
On
Off
On1 second
beep
No
On battery—Output
voltage is out of
range
Off Flashing Off Flashing OnContinuous No
On battery—Output
wave is abnormal
Flashing Flashing Off Flashing OnContinuous No