Hitachi J300 All in One Printer User Manual


 
Turn power
on.
(7
x)
Press con-
tinuousl
y
Data is
stored
Start run
(Motor operates)
000 d 0 F 4 r
F
F 9
03
00F 9
F 2
Data is
stored
Monitoring actual
out
p
ut fre
q
uenc
y
Settin
g
fre
q
uenc
y
to 60Hz
Starting command and set value via
digital operator (instead of terminals)
If reverse run (
r
) is on, forward
run (
F
) can be selected using
the UP or DOWN ke
y
.
F 4
(4
x)
FUNC
.
FUNC
.
FUNC
(3
x)
FUNC
.
FUNC
.
(5
x)
FUNC
0.0
60
.
0
FUNC
RUN
F 2
d
0
FUNC
60
.
0
Data is
stored
(6
x)
Operation procedure (example for the digital operator)
30
.1
30
.
0
29.9
F6
F 6
FUNC
FUNC
F
U
N
C
.
Output frequency
monitor
Motor revolution
monitor
Output current
monitor
Scaled output
fre
q
uenc
y
monitor
Tri
p
monitor
Trip history
monitor
Output frequency
monitor / setting
Set the motor
direction
Set acceleration
time
Set deceleration
time
Manual boost
configuration
Control mode
configuration
FM signal
adjustment
Motor voltage
AVR function
Extended
functions
d 0
d
1
d
2
d
3
d
1
0
d11
F 2
F 4
F 6
F 7
F 8
F
9
F1
0
F11
F14
RUN
After the data has
been changed,
press the FUNC
key to save data.
[FUNC key] ... This key switches
between the parameter area, data
area, and extended function area.
Each time the key is pressed, the
display changes as follows:
[UP key, DOWN key] ... These keys change the
values of data area, and parameters:
[START key] ... This key
starts the J300 inverter.
Set forward or reverse
run using
F 4
.
[STOP key] ... This key
stops the J300 inverter.
When a trip occurs, this key
becomes the RESET ke
y
F14
A0
A1
A96
0
200
FUNC
.
FUNC
.
FUNC
.
FUNC
.
Extended function data
.
Extended function
parameter number
Explanation of display at power on
When the inverter is turned on, the display returns to what was displayed when the power
was last turned off (exce
p
t in the extended function mode).
Settin
g
extended functions
Extended functions are
entered from
F14
using the FUNC key.
Following this, the
function parameter
number is displayed for
which data had been
entered last.
After changes to data
have been made, the
FUNC key must be
pressed. When the
FUNC key is being
pressed once more,
control is returned back
to
A -
-
.
When an extended function is to be used, select the
extended function group by using the two
keys and so as to enter the extended
function mode.
F14
Return to extended
function parameter
and memorize
Display Function
Standard Setting
Set Value
d
0
..
d
3
d10
,
d11
Display functions Refer to page 4
F 2
Set output frequency (Hz) 0.0
F 4
Set motor direction F (forward)
F 6
Acceleration time (s) 30.0
F 7
Deceleration time (s) 30.0
F 8
Configure manual boost 31
F 9
Configure control mode 03
F10
FM signal adjustment 72
F11
Motor voltage AVR function 380
F14
Extended function group Refer to pages 6 and 7
Trip Contents Display
Overcurrent
protection
When the output of the inverter is short circuited,
the motor is locked, or a heavy load is suddenly
applied, and the inverter output current exceeds a
predetermined level, the inverter is shut off.
C
onst
.
s
p
eed
:
E
1/
31
At decelerat
.:
E
2/
32
At accelerat
.:
E
3/
33
At the others:
E
4/
34
Overload
protection
When a motor overload is detected by the electronic
thermal function, the inverter is shut off.
E05
Braking resis-
tor overload
When regenerative braking resistor exceeds the usage
time duration an overvoltage caused by the stop of the
BRD function is detected
,
and inverter out
p
ut is cut off.
E06
Overvoltage
protection
When the inverter DC bus voltage exceeds a pre-
determined level due to regenerative energy from the
motor, this trip occures and the inverter is shut off.
E07
EEPROM error
(NOTE 1)
When the inverter memory has a problem due to
noise or excessive temperature rise, this trip occurs
and the inverter is shut off.
E08
Undervoltage
protection
A decrease of DC bus voltage may result in improper
function of the control unit. It may also cause motor
heating and low torque. The inverter is shut off when
the DC bus voltage goes below a certain level.
E09
CT error When a large noise source is near the inverter or an
abnormality occurs on built-in CT, inverter output is
cut off.
E10
CPU error Malfunction or abnormality of the CPU. The inverter
is shut off.
E11
External trip A trip signal from external equipment shuts off the
inverter. It is necessary to assign the external trip to
an intelligent terminal.
E12
USP error Indicates an error when power is turned on while the
inverter run is enabled
(
with USP function selected
)
.
E13
Ground fault
protection
The inverter is protected by detection of ground
faults between the drive output and the motor at
power on. Protection is for the inverter only and not
for humans.
E14
Input
overvoltage
When the input voltage is higher than a specified
value, it is detected and 100 seconds after power is
turned on, the inverter is shut off.
E15
Short power
down
A short input voltage interruption (>15ms) occured.
The inverter is shut off.
Error in link to
option
1
(option 2)
There is an error in the link to the extension card in
slot 1 (2). The inverter is shut off.
Slot
1:
E17
Slot
2:
E18
Error option 1
(option 2)
There is an error in the extension card in slot 1 (2).
The inverter is shut off.
Slot
1:
E19
Slot
2:
E20
Phase failure One of the power supply phases has broken down.
The inverter is shut off.
E24
J300
This information is written on
the nameplate located on one of
the sides of the J300 inverter.
Mf
g
.No.
Protective Functions
The SJ100 series inverter will trip on overcurrent, overvoltage and undervoltage to protect th
e
inverter.The output is shut down and the motor runs free. This condition is held until it is reset.
J300 data setting values
J300 inverters provide many functions whose parameters can be
set by the user. It is recommended that the parameters that have been set by the user be recorded
N
OTE
1: If an EEPROM error occurs, be sure to observe ist value. If power is turned off while the
[RS] input terminal is held ON, the EEPROM error occurs when power is turned back on.
in order to speed the
investigation and re-
pair in the event of
a failure.
Drive keypad display sequence
HITACHI INVERTER
J300 SERIES
QUICK REFERENCE GUIDE (Part 1/2)
Three phase input 400V
Power Lamp
Power Lamp of
Control Circuit
UP/+ Key,
DOWN/- Key
These keys are
used to change
data and
parameters.
FUNC-Taste
This key is used to
select parameters
and for storing
modifie
d
parameters.
RUN Key
This key is used for
starting using the
direction set by
F 4
.
(When terminal run
is selected this key
does not function).
STOP/
RESET
key
This key is used for
stopping the motor or
resetting errors or trips.
POWER
FUNC
.
RUN
Monitor (LED-Display)
This display shows frequency,
motor current, voltage, motor
direction, and other parameters.
3 4 5