Fire Pump Controllers with LXi Logic
The LED display module is mounted on the enclosure flange, the LED’s are multi-color, red for
critical alarms, yellow for informational indications, and green for status.
A total of (16) LED’s are available to match most any requirement for alarm indications.
Standard Indications for LXi controllers
• Power Available
• Lockout
• Start Time/Acceleration (reduced
voltage/current models only)
• Low Suction
• Locked Rotor
• Pressure Switch Start
• Shorted SCR (LXi-1100 only)
• Fail to Start
• Phase Reversal
• Run Timer
• Pump Start Delay On
• Overload
• Pump Running
• Overtemp SCR (LXi-1100 only)
The LCD display/programming module displays four screens of (4) lines x 20 characters per screen.
Each individual screen may be scrolled in the display by the operator without a password. The LCD
display/programming module is mounted in the enclosure flange.
Main Screen Real Time Information
• System Pressure
• Simultaneous 3-Phase Volts – Phase to Phase
• Simultaneous 3-Phase Amps
(4) Additional LED’s
• Local Manual Start
• Remote Start
• Emergency Manual Start
• Local Manual Stop
The system pressure settings are set using
the touch pad after a password is entered .